10/30/2310/30/23 Confirmed with Nick for 11/7/23 at 9:30am DH / Sent email regarding inspection DH 10/2/23MV Emailed Nick regarding inspection date 10/5, waiting on confirmation Sprinkler Inspection Annual Fire Sprinkler Inspection Deficiency: Townhouse number one will need a sprinkler gauge
8/17/23 confirmed Mayo SM Portable Extinguishers and Emergency / Exit Lights Inspection Annual Fire Extinguisher Inspection (7 FE - 2 on site for this location, and Mayo will bring others from other stores to this location for inspection together) Annual Load Testing Inspection for Exit/Emergency Lighting (2 EE?) Deficiency: Number of Extinguishers Left at Job: 2 Customer replaced units with new 5# abc fire extinguishers.
10/4/22 Confirmed with Nick for 10/12/22 at :00am DH 9/20/22 Confirmed with Sue for 9/21/22 Customer a no show DH Sprinkler Inspection Annual Fire Sprinkler Inspection Deficiency: (Main building) Pressure gauge is outdated. Deficiency: (Main building) There is no evidence of 5 year FDC check valve inspection. Deficiency: (Main building) There is no evidence of 5 year FDC hydrostatic test. Deficiency: (Main building) There is no evidence of 5 year internal pipe obstruction investigation. Deficiency: (Building 17130) Pressure gauge is outdated. Deficiency: (Building 17130) There is no evidence of 5 year FDC check valve inspection. Deficiency: (Building 17130) There is no evidence of 5 year FDC hydrostatic test. Deficiency: (Building 17130) There is no evidence of 5 year internal pipe obstruction investigation. Deficiency: (Building 17130) Missing spare head box and universal head wrench. Deficiency: (Building 3) There is no evidence of 5 year FDC check valve inspection. Deficiency: (