2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Local Reviews
for kalamazoo, mi

Rated 4.6 out of 5 stars based on 50 customer reviews

Great service

Prompt, professional service.

  • Overall Experience
  • Quality
  • Convenience
  • Recommend

Adequate service

Service was interrupted several times by "emergencies" in other areas thus making the overall job take longer.

  • Overall Experience
  • Quality
  • Convenience
  • Recommend

Exceptional Service

The gentleman that came out was great, was able to get what we needed fixed. Very timely.

  • Overall Experience
  • Quality
  • Convenience
  • Recommend

good service ,e3cellent technician

Thanks for your Quick service and professional work by Tyler

  • Overall Experience
  • Quality
  • Convenience
  • Recommend

Inspection Of Building 10

  • Overall Experience
  • Quality
  • Convenience
  • Recommend

Good service friendly.

  • Overall Experience
  • Quality
  • Convenience
  • Recommend

very nice staff

  • Overall Experience
  • Quality
  • Convenience
  • Recommend

very nice staff

  • Overall Experience
  • Quality
  • Convenience
  • Recommend

very nice staff

  • Overall Experience
  • Quality
  • Convenience
  • Recommend

very nice staff

  • Overall Experience
  • Quality
  • Convenience
  • Recommend

Job Locations
for kalamazoo, mi

David H.

David H. Job Checkin


David H.

David H. Job Checkin


David H.

David H. Job Checkin


Mike R.

Mike R. Job Checkin

Deficiency: The duct detector on RTU 1 does not trip and needs to be replaced. Checked it for proper wiring. The only way to get it to trip the panel is to short the wiring. The System Sensor RTS has power, 27v from the dd but has no led lit up and, does not work. This should also be replaced. I tested another random RTS and it functioned properly. Compared wiring from the switch to dd circuit board for RTU 1 and RTU 2 and, it is the same. Models are: Duct detector: System Sensor D4120 RTS: RTS2-AOS


Tyler H.

Tyler H. Job Checkin

FACP BLDG. 9 TELECOM ROOM: MDF-300 MODULE IN BLDG 9 IS BAD AND NEEDS TO BE REPLACED. - repair FACP BLDG. 17 TELECOM ROOM: MDF-300 Moule in bldg 17 is bad and needs to be replaced - repair FACP BLDG. 13 TELECOM ROOM: MDF-300 module in building 13 is bad and needs to be replaced. - repair MP BLDG. 7 BY 204: MP Building 7 by 204 is rusted shut and needs to be replaced - repair MP BLDG. 3 BY 204: MP Building 3 by 204 is rusted shut and needs to be replaced. - repair FACP BLDG. 2 TELECOM ROOM: MDF-300 in building 2 is bad and needs to be replaced. - repair


Tyler H.

Tyler H. Job Checkin

Annual Sensitivity Testing of Smoke Detectors (162 SD) Sensitivity Testing Inspection


Tyler H.

Tyler H. Job Checkin

Annual Fire Alarm Inspection (333 Devices) (Potter PFC 9000) Per Oshtemo Twp FD, batteries need to be replaced every 2 years.


William S.

William S. Job Checkin

Wet: Remove and replace (3) outdated gauges on the fire pump and controller, (1) on the jockey pump, (1) main feed, (4) on the four floor controls, (2) on the standpipe, and (1) on the suction side of the fire pump. NFPA 25 (13.2.7.2) Gauges shall be replaced every 5 years Wet: Perform a 5-year internal inspection of system check valve, bypass check, and 1st-floor check valve. NFPA 25 (13.4.1.2) Alarm valves and their associated strainers, filters, and restrictions orifices shall be inspected internally every 5 years unless tests indicate a greater frequency is necessary. Wet: Perform a 5-year internal inspection of the Fire Department Connection (FDC) check valve. NFPA 25 (13.4.2.1) Check valves shall be inspected internally every 5 years to verify that all components operate correctly, move freely, and are in good condition. Wet: Perform a 5-year Hydro-Static test on the Fire Department Connection (FDC). NFPA 25 (13.8.5) The piping from the fire department connection to th


Art L.

Art L. Job Checkin

Kitchen Suppression Inspection


William S.

William S. Job Checkin

Quarterly Fire Sprinkler Inspection (1 Wet System)


William S.

William S. Job Checkin

Perform a 5-year internal assessment of system piping that is due. If an obstruction is present, this can render the sprinkler system to not properly operate in the case of a fire (19' lift needed). NFPA 25 (14.2.1.1) An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years or in accordance with 14.2.1.2 for the purpose of inspecting for the presence of foreign organic and inorganic material. Perform a 5-year internal inspection of the system check valve. NFPA 25 (13.4.1.2) Alarm valves and their associated strainers, filters, and restrictions orifices shall be inspected internally every 5 years unless tests indicate a greater frequency is necessary. Wet Sprinkler: Perform a 5-year internal inspection of Fire Department Connection (FDC) check valve. NFPA 25 (13.4.2.1) Check valves shall be inspected internally every 5 years to verify that all components operate correctly, move freely, and are in good condition. Perform a 5-year Hydro-S


Tyler H.

Tyler H. Job Checkin

EMCOR Paperwork Attached Problem Location: Interior - fire panel Description of Work: TITLE: AC zone alarm DESCRIPTION: [RT2] Bell 2 Trouble - (Zone ) " " - signal from Transmitter ID #2666 at your facility. This is a trouble signal that indicates a need for service on your system.


Tyler H.

Tyler H. Job Checkin

Annual Fire Alarm System Inspection


John  R.

John R. Job Checkin


Tyler H.

Tyler H. Job Checkin

Annual Fire Alarm Inspection - (21) Systems / approx. (377) total Devices