2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Job Locations
for madison heights, mi


Map of Madison Heights MI
Jim S.

Jim S.


Job Checkin

1/13 Service requested by Connie. She understands the non-compliance. This store will be torn down and rebuilt brand new maybe this year, but meanwhile, they want to keep the links changed etc. km Kitchen Suppression Inspection Semiannual Kitchen System Inspection Ansul R102-S3 (3)360 links (4)Nozzles Ansul R102-S3 (3)280 links (5)Nozzles Ansul R102-S3 (3)360 links (5)Nozzles Deficiency: Number of Systems failed : 3 Deficiency for Ansul R-102 3 Gallon Right of Grill Hood: Discharge warning device does not operate during system actuation on all three systems. Deficiency for Ansul R-102 3 Gallon Right of Grill Hood: Improper nozzle protection over grills. Deficiency for Ansul R-102 3 Gallon Right of Grill Hood: Filet Fryer and Grill Hood systems have red button automan.