Job Checkin

Deficiency: A 500 degree temperature link will be installed in the duct detector with a 350 degree temperature dot stuck on it. The dot will let us know if the heat in the plenum area is exceeding 350 degrees. FSM will only do this if the customer agrres to let us back in within 72 hours to check the dot and verify the temperature isn't exceeding 350 degrees. Deficiency: This location has had the kitchen suppression system above the 3 vat fryer trip 3 times since October 30, 2020. When Fire Systems of Michigan was on site it was determined the fans were intermittently shutting off, which was causing the temperatures above the cooking equipment to rise more than they would if the fans were operating normally, and thus the kitchen fire suppression systems were tripping. The Ansul manual states that a 280 degree link should be used for this line up. Due to the fact fans are shutting off intermittently the customer requested that we put a 500 degree link above the middle fryer until the fa