Alex R.

Alex R. Job Checkin

Arrived On-Site Found FACP in trouble Upon Arrival (Panel Trouble Light for Partial System Disable was lit-and LCD Stated audio visuals Disarmed “meaning Disabled” ) Somebody On-site Disabled Horn/Strobes and when a fire drill was done by pulling a pull station. None of the Horn/strobes would go off because the Horn/strobes had been disabled. Re-Enabled Horn/Strobes and Tested System. Walked entire school making sure that all the Horn/strobes were sounding in the school. Reset System ***All Systems Normal and Reset ***


Alex R.

Alex R. Job Checkin

Arrived On-Site Found FACP in trouble Upon Arrival (Panel Trouble Light for Partial System Disable was lit-and LCD Stated audio visuals Disarmed “meaning Disabled” ) Somebody On-site Disabled Horn/Strobes and when a fire drill was done by pulling a pull station. None of the Horn/strobes would go off because the Horn/strobes had been disabled. Re-Enabled Horn/Strobes and Tested System. Walked entire school making sure that all the Horn/strobes were sounding in the school. Reset System ***All Systems Normal and Reset ***


Alex R.

Alex R. Job Checkin

Arrived On-Site FACP Stating Ground Fault West Electrical Room Remote Power Supply # 7. Located Power supply and checked wiring for grounds (found none) all wiring was secured and no grounds were present. Checked and load tested batteries. Both 12 volt 5 ah batteries were expired and both failed showing (Flat battery status on load tester.) Also the batteries were cracking and bubbled Replaced the 2-12 volt 5 ah batteries and Reset System ***All Systems Normal and Reset ***


Alex R.

Alex R. Job Checkin

Replaced Extinguisher That was Discharged by student 10-lb ABC


Jeff D.

Jeff D. Job Checkin

Portable Extinguishers Service Call


Jeff D.

Jeff D. Job Checkin

Portable Extinguishers and Emergency / Exit Lights Inspection


Jeff D.

Jeff D. Job Checkin


Jeff D.

Jeff D. Job Checkin


Alex R.

Alex R. Job Checkin

Made Deficiency For Boys Athletic Locker Room Damaged Strobe and Requested Cages be ordered as well to protect Devices from damage


David H.

David H. Job Checkin


David H.

David H. Job Checkin


Alex R.

Alex R. Job Checkin

Completed Emergency Service Call Recommend Contacting Simplex to check I/o 9 On Nac I/o board


Jeff D.

Jeff D. Job Checkin


Alex R.

Alex R. Job Checkin

Installed 2-cages over east wall Horn/Strobes in upper aux gym


Alex R.

Alex R. Job Checkin

Replaced Horn/Strobes from inspection