Annual Fire Alarm Inspection (27 devices) (Firelite MS 1OUD)
FACP is currently being monitored by TYCO through 2 dedicated phone lines. It is being monitored using a Honeywell vista 128-FBPN. We should be able to install a Telguard to the vista panel to switch to commercial monitoring. QUOTE Commercial fore for a cell install. - repair
Louisha called (269-883-2188) said the panel keeps going off- said it's showing telco tbl
Annual Fire Alarm Inspection FACP in Electrical Room by Riser Room Edwards IO Series, 5 boosters, 13 smokes, 2 heats, 11 manual pulls, 33 hornstrobes, 22 stobes, 90 A/v’s (in room av’s) 45 rooms total - 2 av’s per room.
COMMERCIAL FIRE PAPERWORK ATTACHED: Install the cover that is missing on the concealed sprinkler head in the Cafe (8' ladder needed).
**Commercial Fire Paperwork** Annual Fire Alarm Inspection
Per email from Becky, they have an ongoing issue with a fire alarm panel beeping off and on throughout the day. Call Becky when on your way- 269-344-8686
Perform a 5-year Hydrostatic test on the Fire Department Connection (FDC). NFPA 25 (13.8.5) The piping from the fire department connection to the fire department connection check valve shall be hydrostatically tested at 150psi (10 bar) for 2 hours at least once every 5 years.
Remove and replace a section of the 4" sprinkler piping that has a temporary patch due to a leak. The location of the piping is in a tight area and will require the piping to be cut into several pieces. Access to the leak is through the kitchen on the 2nd floor. THe pipe is to the right on the 2nd 4" tee. During the repairs completed on 1/21/2022, the tech found that there was a leak on 4" sprinkler piping in the attic. Attic access is in the dining room in hall E1 by Scott's office. Tech will replace a section of the sprinkler piping.
This quote is to replace the bad Door Holder BY LAUNDRY ROOM 7769 . This device failed on the inspection and needs to be REPLACED - repair
Annual Fire Alarm Inspection 1 FACP, 3 smokes, 4 manual pulls, 3 Av's Bi-Annual Sensitivity Testing (3 smokes)