2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Local Reviews
for redford charter township, mi

Rated 5.0 out of 5 stars based on 6 customer reviews

Excellent service - prompt, professional, easy to understand potential sources of the issues

Tony responded promptly and met me at the facility. He patiently explained what happened, potential causes and recommended next steps. I will request him for our upcoming annual inspection and even consider switching our fire protection service from our current provider to Fire Systems based on my positive experience. I appreciate he mentioned this is a service you provide.


Response from Fire Pros Inc:

Thank you so much Kym for sharing your positive experience with our company and our technician. We appreciate your business.

  • Overall Experience
  • Quality
  • Price
  • Convenience

great job

done timely

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great

Great Guy vary knowledgable

  • Overall Experience
  • Quality
  • Price
  • Convenience

Very professional, competent and respectful

  • Overall Experience
  • Quality
  • Price
  • Convenience

Fantastic customer service

Corey came to our location for the first time to inspect our fire extinguishers. He was personable, professional and very thorough in his work. A great asset to the company!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Awesome Service

Sean is awesome!! When I came to open the facility, I was no longer angry about getting up early when I saw Sean! He's personable and extremely professional. He is knowledgeable, friendly and extremely Punctual! I would recommend him to any business looking for a great personality and the expertise to match! This is my second encounter at a second location and the quality that he offers is impressive! Thanks Sean for the wonderful service!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for redford charter township, mi

Jared J.

Jared J. Job Checkin

Portable Extinguishers Inspection


Tony K.

Tony K. Job Checkin

Alarm Systems Emergency Service Call


Alex R.

Alex R. Job Checkin

Arrived On-Site Front Inner Door Corby Key Pad was non-Functional. After further investigation I found the Ground Static collar violet wire disconnected causing key pad to lock up and cease functions. Per. Corby Installation Cut-Sheet Violet static collar wire must be connected to prevent static discharges to key Pad. Replaced Key Pad, Wired, and Programed Key Pad, and Reconnected static ground Collar, and Tested ***All Systems Normal and Reset ***


Alex R.

Alex R. Job Checkin

Arrived On-Site Building was in Active Fire Alarm Mode With Kitchen Smoke Detector in Alarm. Found smoke Detector Removed and Wires partially disconnected. Attempted to clean smoke Head and re-Fastened Wiring and attempted System Reset. System would not reset was later informed that smoke detector was water damaged earlier in the week. Replaced smoke detector and Base and re-programed Detector type and Tested new Head and Reset System ***All Systems Normal and Reset ***


David H.

David H. Job Checkin


Jim S.

Jim S. Job Checkin


Alex R.

Alex R. Job Checkin

***Customer stated He has supervisory on Panel and Requests Emergency Service*** Arrived On-Site FACP States Supervisory Tamper Boiler Room Sprinkler North Hallway (M33 P 077) Located Sprinkler Tamper Switches (2-OSY VALVES) Found Excessive grease build up in groove where Tamper Switch Arm Rests. Removed Grease build up. And reset Switch ***All Systems Normal and Reset ***


David H.

David H. Job Checkin


Alex R.

Alex R. Job Checkin

Customer calling about front Door Mag Lock Releases On it's own. Wants Emergency Service to check. Arrived on-site found front door dyna Lock was releasing on its own momentarily after code being entered. Door would Un-Lock Normally and then secure it self normally. (But then the Key Pad would momentarily disarm buzz and unlock Mag Lock and then Re-Arm it self). Re-Programmed Corby Key Pad and Tested multiple times ****All Systems Normal and Reset ****


Alex R.

Alex R. Job Checkin

Customer calling about front Door Mag Lock Releases On it's own. Wants Emergency Service to check. Arrived on-site found front door dyna Lock was releasing on its own momentarily after code being entered. Door would Un-Lock Normally and then secure it self normally. (But then the Key Pad would momentarily disarm buzz and unlock Mag Lock and then Re-Arm it self). Re-Programmed Corby Key Pad and Tested multiple times ****All Systems Normal and Reset ****


Corey  B.

Corey B. Job Checkin


Jacob F.

Jacob F. Job Checkin


Sean W.

Sean W. Job Checkin


Dan S.

Dan S. Job Checkin

Spoke to Shanquika Portable Extinguishers Inspection Annual Fire Extinguisher Inspection (17 units) Deficiency: they need a cabinet key. 151 key Deficiency: need 8 new Plains of glass for cabinets 10 in wide and 21 in long