Sprinkler Inspection Annual Sprinkler Inspection Deficiency: Site is missing an ESC. Deficiency: All fire systems are due for gauge change a total of three.
10/10/22 Sent email regarding inspection DH Sprinkler Inspection Quarterly Fire Sprinkler Inspection (1 Wet System)
Completed annual Fire Extinguisher inspection for 2022
12/8/21 confirmed with jessica for Monday 12/13/21 sm Kitchen Suppression Inspection Semi-annual Kitchen System Inspection Deficiency for Ansul R-102 6 Gallon Main hood: 6 Gallon system needs manifolded bursting disc installed. Deficiency for Ansul R-102 6 Gallon Main hood: Pull station center piece missing. Needs a new one.
10/4/21 Caleed and they say they will Schedule this week SM Kitchen Suppression Inspection Semi-Annual Kitchen Suppression System Inspection Ansul R102-S3 (3)360 links (6)Nozzles Deficiency: Number of Systems failed : 1 Deficiency for Ansul R-102 3-Gallon Right Of Hood: System is out of hydro date. Deficiency for Ansul R-102 3-Gallon Right Of Hood: System does not have a discharge warning device. Deficiency for Ansul R-102 3-Gallon Right Of Hood: Detection line has 2 two piece link holders that need to be replaced.