2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Job Locations
for sterling heights, mi


Map of Sterling Heights MI
Terrence  J.

Terrence J.


Job Checkin

1/5/24 Key at Darlena's Desk DH 12/22/23MV Emailed Ashley regarding inspection date 12/26 Sprinkler Inspection Annual Fire Sprinkler Inspection (1 Wet System) 5-Year Internal Due: N/A CPVC Piping FDC Hydro Due: 2024 Deficiency: 155 chrome QR chrome pendants are older than 20 years old and 4 x will need to be pulled and sent in for UL testing Deficiency: Sprinkler system is due for gauge change. 1- sprinkler gauge Deficiency: Dry pendant, sprinkler heads in garage are more than 10 years old and should be tested or replaced 2- 155° chrome pendant, dry pendant, sprinkler head standard response length unknown Deficiency: 155 chrome QR chrome pendants are older than 20 years old and 4 x will need to be pulled and sent in for UL testing. 4- 155° chrome pendant sprinkler heads quick response