6/29 - Left message to move inspection time to 12-12:30  p.m.   mh 6/25 Approved by Shelly (anytime after 10:00 AM) She'll be there to let us in.km Kitchen Suppression Inspection Semiannual Kitchen Inspection Ansul R101-30 (1)360 link (6)Nozzles Suggested: The Fire-Lite FACP Batteries are Due for Replacement 2-12 volt 8 ah batteries Recommend Replacing existing Radionics Battery with larger 12 volt 7ah battery Deficiency: The system is r-101 and needs to be upgraded due to being out of date Deficiency: 1 5lb abc fire extinguisher is due for 6yr maintenance, but it’s a 2008, and was also 6yrd in 2013. I recommended that they replace due to it needing replacement in 2020.