12/4/23 Confirmed with Matt for 12/14/23 at 8:00am DH Sprinkler Inspection Annual Fire Sprinkler Inspection (2 Dry Systems) 5-Year Internal Due: 2024 FDC Hydro Due: 2024 Deficiency: Recommend a complete walk thru of both systems to locate leaks in piping and materials gathered for repairs before a full flood test can be completed. Deficiency: Out dated dry heads are due for testing. Only 2 installed in kitchen, replace. (1) 12β 200 SR chrome dry pendant (1) 18β 200 SR chrome dry pendant (1) can of spray foam Will have to fab in head for freezer, current head is a 12β Deficiency for 2.5 lb ABC outside smoking: This compressor is on itβs last leg it was knocking pretty bad and is not engaging and disengaging properly the system has leaks and this compressor has been overworked this pro compressor will need to be replaced as soon as possible. Deficiency: The system air compressor is starting to go bad the compressor has been in system for some years now with piping leaking the bed mo
3/29/23MV / DH Confirmed with Oscar R. for 4/3/23Emailed customer regarding inspection date 4/6, waiting on confirmation Sprinkler Inspection Quarterly Fire Sprinkler Inspection (2 Dry Systems)
Sprinkler Warranty Call Warranty call for trouble with new compressor
1/30/23mv Left a VM with Oscar regarding inspection date 1/31, waiting on confirmation 1/20/23mv emailed customer regarding inspection date 1/25, waiting on confirmation Sprinkler Inspection Quarterly Fire Sprinkler Inspection (2 Dry Systems)
Sprinkler Inspection Quarterly Fire Sprinkler Inspection (2 Dry Systems)
Completed annual Fire Alarm inspection for 2021