11/12 Confirmed with Alex and the kitchen guy. Start with extinguisher inspections, then move to kitchen around 12:30 pm km Kitchen Suppression and Portable Extinguishers Inspection Semi-annual Kitchen System Inspection Ansul R102-S3 (1)360 link (4)Nozzles Ansul R102-D6 (3)360 links (8)Nozzles Annual Extinguisher Inspection ( 19 ABCs , 2 Ks ) Deficiency: kitchen surpression small kitchen needs 245 raised to 40" currently 36" Deficiency: kitchen surpression ---small kitchen--- small kitchen needs 245 raised to 40" currently 36" or nozzle changed to 260 debris found inside tank replace chemical (3) gallons ansul-ex —main kitchen—— Regulator dated 1999 needs replaced Pull station blocked must maintain 36” clearance


Terrence  J.

Terrence J. Job Checkin


John  R.

John R. Job Checkin


David H.

David H. Job Checkin


David H.

David H. Job Checkin


Terrence  J.

Terrence J. Job Checkin


Terrence  J.

Terrence J. Job Checkin


Terrence  J.

Terrence J. Job Checkin


David H.

David H. Job Checkin


Jared J.

Jared J. Job Checkin

Portable Extinguishers Inspection


David H.

David H. Job Checkin


Sean W.

Sean W. Job Checkin


Tony K.

Tony K. Job Checkin

Annual Fire Alarm Inspection


Alex R.

Alex R. Job Checkin

Completed Sensitivity Testing on 3 Smoke Detectors and Reset System ***All systems normal and reset ***


Alex R.

Alex R. Job Checkin

Completed Annual Fire Alarm inspection for 2018