2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Job Locations
for superior charter township, mi


Map of Superior Charter Township MI
Alex H.

Alex H.


Job Checkin

11/12 Confirmed with Alex and the kitchen guy. Start with extinguisher inspections, then move to kitchen around 12:30 pm km Kitchen Suppression and Portable Extinguishers Inspection Semi-annual Kitchen System Inspection Ansul R102-S3 (1)360 link (4)Nozzles Ansul R102-D6 (3)360 links (8)Nozzles Annual Extinguisher Inspection ( 19 ABCs , 2 Ks ) Deficiency: kitchen surpression small kitchen needs 245 raised to 40" currently 36" Deficiency: kitchen surpression ---small kitchen--- small kitchen needs 245 raised to 40" currently 36" or nozzle changed to 260 debris found inside tank replace chemical (3) gallons ansul-ex —main kitchen—— Regulator dated 1999 needs replaced Pull station blocked must maintain 36” clearance