Dry: The technicians responded to a service call the customer submitted for issues with the dry system. The technicians were not able to find any visible leaks throughout the attic. The dry system was losing about 1lb of pressure per minute when onsite. The air compressor with the bypass closed is unable to keep up with the demand which is causing the system to trip. The system was tripped upon arrival but there were no signs of water damage. Having a tow behind the air compressor that pushes heavier pressure through the system is recommended to hear where the leak is coming from. NOTE: Once the leak is found and patched, additional material will be billed accordingly. Sprinkler Repair