3/22/24 Material in shop in Novi DH 3/13/24 (EA) Marta emailed requesting a scheduled date for this work. She said it would have to be a Monday or Weds. She confirmed the date 3/25/24 Sprinkler Repair The tech will remove and replace the outdated water gauges on both risers. NFPA 25 (13.2.7.2) Gauges shall be replaced every 5 years The latch line above the control valve is to be piped. INFORMATIONAL PURPOSE ONLY: The hydraulic Placard on the system describes the system design and capacity. The current one for both systems are missing. We suggest that the customer reaches out to the installing company to request this information. This would be the most cost-efficient way to achieve the need. Or the customer can contact Fire Pros for a quote to have our engineer go onsite to obtain the information. **We have excluded any pricing in this proposal for addressing this issue. NFPA 13 (24.5.1) The installing contractor shall identify a hydraulically designed sprinkler system with a per