Very helpful, informative and took the time to explain each inspection.
1/19 Requested and confirmed with Tanathan via emails. FM issue Do not miss km Kitchen Suppression Inspection Semi-Annual Kitchen Suppression System Inspection Deficiency: Electric non fuel source on deep fryers 4,5,6 does not de energize upon fire system actuation. Deficiency: 6- 290 nozzles old and worn out tips blow off caps will not stay on causing nozzles to clog. Deficiency: Number of Systems failed : 1
1/25 Confirmed with AK for 8:00 KM 1/14 approved by Andrea Jones. LM for Mgr. km 1/6 Emailed team km Kitchen Suppression, Portable Extinguishers, and Emergency / Exit Lights Inspection Semi annual inspection of the kitchen system Annual inspection of the fire extinguishers Annual inspection of the e/lights 90 minute load test Deficiency: Number of Systems failed : 1 Deficiency: Henny Penny protection is improper. Need to replace lower nozzle on each kit. Deficiency: PCL-600 tank out of hydro date. Inoperable Deficiency: Electric fuel source on heat cabinet and electric gas oven does not shut down during system actuation. Inoperable Deficiency: Electric outlet 110v in center of hood near floor not working prior to test. Deficiency: Electric 110v outlet center of hood near filter bank does not shut down during system actuation. Deficiency: Copper tube from control head to PCL-300 tanks is more than 14 feet. Inoperable Deficiency: Exit light batteries in dining room exit lights need t
1/20 Confirmed with Alexis via text. She'll be on site for you. km 1/14 Approved by Andrea with mgr cell phones. LM For Alexis km 1/6 Emailed Team, UNCONFIRMED km Kitchen Suppression, Portable Extinguishers, and Emergency / Exit Lights Inspection Semi annual inspection of the kitchen system Annual inspection of the fire extinguishers Annual inspection of the e/lights 90 minute load test Deficiency: Number of Systems failed : 1 Deficiency: Electric connections are made inside of automan. Deficiency: Both expellant cartridges are out of hydro date. Deficiency: Number of Extinguishers Left at Job: 1 Deficiency: K-Class fire extinguisher out of hydro date. Inoperable Deficiency: 5- 6v-5a E-Light Batteries
12/29/2020 - Brett (GM) approved the appointment for 1/5/2021 at 7am. Kitchen Suppression Inspection Semiannual Kitchen System Inspection Ansul R102-T9 (10)links (16)nozzles Deficiency: Number of Systems failed : 1
12/14 Confirmed with Andrea via emails km Kitchen Suppression, Portable Extinguishers, and Emergency / Exit Lights Inspection Semi annual inspection of the fire system Annual inspection of the fire extinguishers Annual inspection of the e/lights Deficiency: Deep Fryer is undetected. Detector bracket is centered in duct. Deficiency: 3 Holes in plenum are unplugged. Deficiency: Detector brackets in both ducts are not centered in the duct. Deficiency: Plenum nozzles are positioned incorrectly. Deficiency: Number of Systems failed : 1 Inoperable Deficiency: 2- Exit lights in kitchen need batteries replaced.
9/14 - Mitch called in for service 519-410-7710 . Please do not miss. FM issue 6/24 LM for Emad km 4/23 @ 4:12 called to schedule NW 3/19-Called Emad to schedule NW Kitchen Suppression and Portable Extinguishers Inspection Semi-Annual Kitchen Suppression System Inspection Annual Fire Extinguisher Inspection
NOTICE OF NON-COMPLIANCE AND REPAIR NEEDED Thank you for giving Fire Systems of Michigan the opportunity to service your fire protection needs. This proposal is being presented based on a recent inspection of your Emergency/Exit Lights and is priced to be done during normal business hours. To discuss this proposal, please contact: Rob Harrison Phone: (616) 588-0746 Email: rob.harrison@firepros.com CUSTOMER AGREES TO PAY COMPANY THE FEES OUTLINED BELOW PLUS VEHICLE/FUEL CHARGES THAT MAY BE ASSESSED FOR THE CONTRACTED-FOR EQUIPMENT REPAIR OR REPLACEMENT.Sales tax is included in this quote. If your company is tax exempt, please provide tax exempt or resale certificate, otherwise sales tax will be assessed and must be paid. TERMS: NET 30 DAYS AND THIS QUOTE IS GOOD FOR SIXTY (60) DAYS FROM THE DATE OF ISSUE. COMPANY RESERVES THE RIGHT TO REASONABLY INCREASE THE FEES AND CHARGES AT ANY TIME THEREAFTER. BY SIGNING BELOW OR ELECTRONICALLY APPROVING (VIA APPROVAL/ACCEPTANCE OF THIS QUOTE ONLIN
e/lights are a load test inspection Kitchen Suppression, Portable Extinguishers, and Emergency / Exit Lights Inspection Inoperable Deficiency: System is manual release only. Inoperable Deficiency: 1/4 in. expellant pipe is to great of distance to actuate third tank. Recommend having electrician move electrical box and camera so we can relocate our tank to the proper location. Inoperable Deficiency: Detection line is frayed by fifth link holder. Semi-Annual Kitchen Suppression System Inspection Annual Fire Extinguisher Inspection Annual Emergency/Exit Light Inspection
8/3 Confirmed with Chris, manager to replace tag that fire inspector ripped off. Kitchen Suppression Service Call Replace tag from Semiannual service that was done in April. Fire Inspector came in and told him he was out of date and ripped the tag off.
6/24 Approved by Brent, mgr. He'll be on site, no cooking at 8:00 and he'll manager alarms km 3/13-John confirmed the kitchen suppression inspection/aware of alarms NW Kitchen Suppression and Portable Extinguishers Inspection Semiannual Kitchen System Inspection Ansul R102-T9 (10)links (16)nozzles Annual Fire Extinguisher Inspection
Ansul R 102 9 Gallon: Semiannual Inspection of Ansul 9 gallons system Kitchen Suppression Inspection 3/12-Thomas confirmed the kitchen suppression inspection/aware of alarms NW
3/12-Krista confirmed the semi-annual kitchen suppression inspection/aware of alarms NW Portable Extinguishers and Kitchen Suppression Inspection Annual Extinguisher Inspection Semiannual Kitchen System Inspection Deficiency for R-102 6G chase: No electric non fuel source shut down on filet fryer and grill system. Deficiency for R-102 6G chase: Surface protection piping from plenum supply line is galvanized pipe. Fittings from that point are also galvanized. Pipe coming from plenum to surface are welded in the hood.