Sprinkler Repair During the recent sprinkler system inspection performed by Liberty Fire Solutions, LLC the following deficiencies were found. Fire Department Connection is due for the 5 year hydro test per NFPA 25 6.3.2.1 Hydrostatic tests of not less than 200 psi (13.8 bar) pressure for 2 hours, or at 50 psi (3.4 bar) in excess of the maximum pressure, where maximum pressure is in excess of 150 psi (10.3 bar), shall be conducted every 5 years on manual standpipe systems and semiautomatic dry standpipe systems, including piping in the fire department connection. 13.7.4 The piping from the fire department connection to the fire department check valve shall be hydrostatically tested at 150 psi (10 bar) for 2 hours at least once every 5 years. FDC is due for the 5 year hydrotest 2-2.5†hose connections. On front porch - repair