Semi-Annual Kitchen Suppression Inspection Equip Desc: ANSUL R-102 -- CAFETERIA KITCHEN
Semi-Annual Kitchen Suppression Inspection Equip Desc: RANGE GUARD RG4GM -- CAFETERIA KITCHEN Deficiency for RANGE GUARD RG4GM 4G CAFETERIA KITCHEN: Pull station is 55" and is too high for code requirements (42-48") Pull station needs lowered to proper height 25' cable
Sprinkler Inspection Annual Sprinkler Inspection (WET System) Suggested: Recommend replacing 2" control valve leaking and deteriorating Currently it is Copper to brass control valve