**confirmed with Barb for mid-day. ** Notice of Non Compliance and Repair Proposal Liberty Fire Solutions recently inspected/serviced the fire sprinkler system at your establishment in accordance with applicable state statutes, local fire codes and NFPA guidelines. While inspecting/servicing your fire sprinkler system, it was determined to be "Non-Compliant" per local fire codes. The attached proposal summarizes the non-compliance issues that were found during the inspection/service and the costs and actions needed to correct them. The sprinkler systems are due for a 3 year pressure test of the dry system per NFPA 25. NFPA 25 REQUIREMENTS FOR  YEAR TESTING: NFPA 3.4.3.2.6 With the system at normal system pressure, shut off the air source (compressor) for 4 hours. If the low air pressure alarm goes off within this period, the air leaks shall be addressed. Notice of Three Year Dry Sprinkler System Pressure Test Proposal Liberty Fire Solutions recently inspected/serviced the fire sprinkle