Found both VHL Griddle pilots not lighting intermittently. Found low MV signal from thermocouple. Removed and replaced both thermocouples. Found high gas pressure, 13" wc. Could not adjust due to regulator vent being blocked. Removed and replaced regulator and set to 4"wc per data tag. Lit pilots and checked operation, unit operating normally at this time.