I am finishing a heating repair in the heart of Roswell today. Diagnosed Goodman GMVC96 furnace producing insufficient heat. Found restricted gas valve due to debris. Cleaned valve, adjusted gas pressure from 2.8" to 3.5" WC, and verified proper manifold pressure. Heat output now meeting specifications.