Perform Planned Maintenance on Lab Hood
Perform Planned Maintenance on Ice Machine
Troubleshoot and Repair HVAC Equipment
Troubleshoot and Repair HVAC and Ice Machine
Inoperable Deficiency for 2nd Floor Mechanical Room Fan#17 BHM07872 Upflow Exhauxt Harrington HPC-1050 1226-91-3: Responded to call of exhaust fan not operating properly - Switched on hood inside space - Switched unit on at blower assembly - Belt off on arrival - Bearings can be seen with collar broken away from bearing assembly - Pulley’s are also in bad shape - Put belt on system and adjusted tension - Switched on and bearings are going to need to be replaced - Switched system back off until repairs can be made Will quote repairs needed to get system back operational Deficiency for Scotsman CME506AS-1H BHM05764 07031320014923 Boat house: Responded to second call of ice machine not producing normally - System was not running at first inspection - Controller light flashing water indication for little to no water flow - Found incoming water filter and tank filled with rust - Isolated water, rinsed water filter and canister - Flushed lines until water ran clear - Reinstalled canister an
HVACR and Ice Machine Planned Maintenance