2430 Reliance Ave
Apex, NC 27539
919-773-9223

Job Locations
for new hill, nc


Map of New Hill NC
Matt P.

Matt P.


Job Checkin

Inoperable Deficiency for 2nd Floor Mechanical Room Fan#17 BHM07872 Upflow Exhauxt Harrington HPC-1050 1226-91-3: Responded to call of exhaust fan not operating properly - Switched on hood inside space - Switched unit on at blower assembly - Belt off on arrival - Bearings can be seen with collar broken away from bearing assembly - Pulley’s are also in bad shape - Put belt on system and adjusted tension - Switched on and bearings are going to need to be replaced - Switched system back off until repairs can be made Will quote repairs needed to get system back operational Deficiency for Scotsman CME506AS-1H BHM05764 07031320014923 Boat house: Responded to second call of ice machine not producing normally - System was not running at first inspection - Controller light flashing water indication for little to no water flow - Found incoming water filter and tank filled with rust - Isolated water, rinsed water filter and canister - Flushed lines until water ran clear - Reinstalled canister an