Today I came out to your home to assess the HVAC system tripping its breaker. Upon arrival, we discussed how often the issue has been occurring and whether there were any other electrical concerns present. You explained that the home was recently purchased and that you are planning to move in within the next couple of weeks. With your approval, I performed a comprehensive visual assessment of your home’s electrical system, including the interior electrical panels, grounding and bonding systems, safety equipment, outdoor meter space and meter base, and the crawl space. During this evaluation, several significant safety concerns were identified that impact both system reliability and overall household safety. The furnace was found to be installed on a GFCI breaker (Shock Guard Protection) due to previous modifications where the dedicated furnace circuit was extended to supply receptacles for condensate pumps and air purifiers. This configuration can contribute to nuisance tripping and i