Today I came out to your home to assess an issue with the air handler wiring that had melted inside the unit. Upon arrival, we discussed the current concerns, and you explained that the home had smelled like smoke, which led you to have your HVAC technician inspect the system. During that inspection, a melted electrical connection was discovered inside the air handler, prompting today’s visit. With your approval, I performed a full visual assessment of your home’s electrical system to ensure it was safe to operate and service. This included inspecting the electrical panels, grounding system, safety components, and the crawl space. During the evaluation, several serious safety issues were identified and brought to your attention. The emergency heat strip wiring was found to be undersized, and the wire nuts used were too small for the conductor size. The air handler is equipped with a 10,000-watt heat strip, yet it was supplied with #8 Romex, which is only rated for 40 amps, creating a