Did a minimum diagnosis on receptacle outside of front door. It had been burned up from the neutral and hot. Installed a new gfci and bubble cover and cut back the burnt wires to the new sheathing. Looked at the panel and the neutral were double tapped. Separated all the neutral and cut the sheet hung back with a new line of copper to have better connections.