Today I came to Marc’s Okotoks home because the 10+ year old boiler has been leaking. Upon inspection I found the condensate trap is leaking. This is caused by a plugged condensate drain. There are also micro leaks on the piping coming in and out of the boiler, and the boiler is giving a warning notice indicating a flame issue. Unfortunately the leak dripped onto the axiom hydronic feeder causing it to fail and it must be replaced. Tax return July 24 to replace axiom system feeder replace condensate drain and to replace ignition on boiler Technician first removed ignition system with flame sensor and installed new one with new gasket and bolts tech then isolated and removed old axiom system feeder installed new one and transferred fluid into new system. Feeder tested for functionality working well tech then cut out old condensation drain and installed new condensation drain in PVC piping tested boiler. System fired up without issues. Client thanked us for coming out today.