9320 S. Pole Rd
Oklahoma City, OK 73160
(405) 794-8900

Our Top Cities


Local Reviews
for mcloud, ok

Rated 5.0 out of 5 stars based on 6 customer reviews

Excellent service

Prompt service. Did a really good job. I have recommended Interstate Heat and Air to others.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Very professional, really pleasant, helped us a lot.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service

  • Overall Experience
  • Quality
  • Price
  • Convenience

Service

Excellent service. Very professional.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Service call

Brandon is very courteous and knowledgable.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Tuneup service

We had a tune up service today with Issac. He did a great job. Very professional.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for mcloud, ok

ISAAC J.

ISAAC J. Job Checkin

Came out to call for a system not cooling properly. Customer stated that the AC system wasn’t on outside. I checked the system over and found the AC had no power. Checked fuses and they were good. Checked the breaker and found it tripped. System is rated for a 45 amp breaker and system has a 30 on it. Recommended replacement of the breaker to proper size. Washed condenser coil thoroughly and rechecked system to test it and verify that everything was working. Found unit just a little overcharged, so I reclaimed some of it to get units pressures in check. System is now cooling properly. Discussed with customer about replacement and ductwork as well. Gave customer a rough estimate based on discussion.


ISAAC J.

ISAAC J. Job Checkin

Came out to call for a system not cooling properly. Customer stated that the AC unit wasn’t coming on, and it was just blowing warm air. Customer replaced the capacitor but unit still wasn’t cooling. I checked system over and found capacitor to be good still, and the fan cap she replaced to be correct. System is completely clogged with debris. After checking the unit I asked them to cycle it on, and it came on with no issues. I believe the fan motor cut out on internal overload and kept the system from cooling. Recommended washing the condenser coil thoroughly and checking refrigerant pressures and operation afterwards. I washed the condenser coil thoroughly and then rechecked operation. System was working properly. Fan motor is operating within proper range at this time. Recommended maintenance plan to keep system maintained. Customer signed up for blue plan. Supplied customer filters to replace when it’s time. This counted as her first service with us.


Rodney S.

Rodney S. Job Checkin

Blue shield summer service x 2. Replaced filters. Blower motors are ECM, run capacitors not required, motors and wheels are clean, indoor coils are clean, condensate drain lines are clear. Condenser coils are clean. Both dual run capacitors tested bad on compressor side. Replaced both capacitors under 10yr part and labor warranty. Contactor points tested good. Checked operation, all amps and pressures are good. Both systems are operating normally.


Joseph K.

Joseph K. Job Checkin

I arrived for a new customer system replacement opportunity. I spoke with the homeowner about what his system is and what he wants to replace it with. He has propane on the location and has propane stubbed into the closet beside the air handler now. We bid 4 options on what the homeowner may want and i explained all options to the homeowner. Any option will come with a 10 year parts warranty and a 2 year labor warranty with a 1 year maintenance plan that will include two services a year to keep the system serviced and clean. Our bids are good for 30 days and can change pricing after the first 30 days. If you have any questions about any systems we discussed please reach out to me and I will be happy to help you in anyway possible. Jake Kring.


Joseph K.

Joseph K. Job Checkin

I arrived for a new customer no cool call. I spoke with the homeowner and found that the system stopped cooling and he replaced the thermostat and transformer. I inspected the system and found the transformer to have failed and a that there was a short to ground and it was still present. I explained I can trace the short out and replace the transformer to see where the power stops. The homeowner agreed to the repair and I replace the transformer and fuses the low voltage. I found the contactor on the condenser to have shorted to ground on the 24V coil side. I offered to replace the contactor and the homeowner wanted to get the part and replace it his self. I left the system correctly wired with the new transformer and the system in the off position. The homeowner will replace the contractor and clean the evaporator coil and blower motor. I explained that if the system is not up and running I cannot check the system to see how it will run and that the system needs to be cleaned. If you


ISAAC J.

ISAAC J. Job Checkin

Came out to call for a system not cooling properly. Customer stated that the AC wasn’t coming on and just blowing room temperature air. Checked system and found no power to the outdoor unit. Went to the breaker box to check breaker and found the breaker not wired up and I couldn’t find which wires where the ones to wire up the AC unit. Recommended customer have an electrician out to rewire disconnect or locate the wires.


Joseph K.

Joseph K. Job Checkin

I arrived for a previous customer no heat call. I spoke with the homeowner and found that the system will run but the air coming out of the vents are weak. I inspected the system and found all 4 heat strips to be operating. I also found the the floor in front on the air handler to be weak and falling through to the underside of the house. This plenum that is condenser to the floor and system is falling apart. I made this aware to the homeowner and tried to explain that the heat is working but it’s blowing all its hot air under the house and the air that is completely out is a mixture of cold and hot air. I recommended to have mobile home repair company come out and see if they could fix it but he insisted that I do the work. I bid to replace all 5 duct runs under the home with metal duct. The homeowner wanted to wait and see if this will keep him comfortable before making a decision.


Joseph K.

Joseph K. Job Checkin

I arrived for a blue member fall maintenance on two system. I Inspected the upstairs system and checked all electrical components and filter to be in good condition. I found some growth in the system and cleaned with rags and cleaner. I then inspected the downstairs system and found the system to be in the same condition as the upstairs system. I then inspected the heat pumps and found them to be running properly. I recommend to install UV lights in the auto keep the systems clean. The homeowner wants to hand cleaning the air handler monthly on their own.


Jason B.

Jason B. Job Checkin

06JAN2021 Jason B Arrived for no heat. Spoke with Homeowner about the situation. It’s doing the same thing as last time. Inspected filter. Filter is very dirty. Inspected furnace and found system locked out on flame rollout sensor. Reset safeties then cycled system. Found burner 3 not lighting properly. Remove filter and cycled system. Checked gas pressure and temp split. Gas pressure was at 3 adjusted it to 3.5 iwc cycle system multiple times found no issues with ignition or temp split. System is running properly at this time. Gave customer clean filter


ISAAC J.

ISAAC J. Job Checkin

Came out to call for a system not heating properly. Customer stated that the system was reading a code and the unit was blowing cold air non stop. I checked system over and found unit reading code 13, which states that the system had entered a lockout mode. This mode is activated due to the amount of short cycling a system does. The unit was being filtered at the unit and in the filter grill. Both filters were overdue to be changed. Though the customer stated the filters were changed a month ago. I recommended that the filter be changed every month, due to location of return and the amount of foot traffic and pets. I checked system operation, gas pressure and temperatures. System is heating properly within manufacturing specifications now.


Mike T.

Mike T. Job Checkin

On September 10, 2021 I arrive to a Blue Shield customer for a two system spring tuneup upon arrival I agree to the customer we then went to the thermostats and turn them on and then Went to the upstairs air handler checked blower wheel clean checked evaporator coal it’s clean did amp draws units pulling 1.1 amp went to the downstairs air handler check the blower wheel it’s clean Checked the evaporator coil it’s clean and then went to the outdoor units the upstairs condensing unit washed it checked capacitor and contactor both are good check the charge unit had 8° sub cooling I then checked the downstairs condenser and I washed it then I checked the capacitor and contactor both are good check to George unit had 10° sub cooling everything ‘s working properly at this time thank you for your business Mike T


Kianoosh M.

Kianoosh M. Job Checkin

Duct cleaning inspection- home has floor ducts over crawl space and is a converted single wide manufacturer home with a solid over cinderblock addition for the master bedroom. The floor ducts are flex and laying pretty loosely on the ground in the crawl space. There are 12 supplies and manufacturer return setup in hall closet. There is evidence of animals having gotten into the ducts at some point, and I explained to the customer that at best we could do an air balance test and search for ductwork to repair under the house. Complete replacement is not really an option due to the way the plumbing is run under the home. Duct. Leaning is also not a feasible option since wen’t thoroughly clean the ducts - we can clean about 5-10 feet in with a shop vac, and the customer said he could do that work with his shop vac. Left an estimate to repair one duct, will need two men to do the work. If we need to repair more than one duct, the repair price will be added on. Customer will test the syst


Jason B.

Jason B. Job Checkin

14AUG2021 Jason B Arrived at new customers home for a call about not cooling well. Spoke with Charles about his systems performance. His thermostat had stopped working and once he got it back up the system wasn’t cooling the home off. Cycled the system on at the thermostat, checked pressures, contactor, and electrical components at the condenser. Inspected the Airhandler and found tape coming off covering a missing plate at the coil. Checked delta T and found a 20 degree temperature split. This system is running properly, but struggling in the humidity. This is a converted trailer home with older windows, and not sealed very well. Taped over coil panel with metal tape.


Joseph K.

Joseph K. Job Checkin

I arrived for a friends and family bid to replace the air conditioner. I inspire system and found the evaporator coil to be dirty and in need of a heavy cleaning or replacement. We decided to bid the outdoor condenser replacement only at this time. I made them aware that if they do decide to replace the evaporator coil that the cost will change. I also bid to clean the coil at the time of the condenser replacement. The bid is to replace the condenser only but the replaced components will have a 10 year parts warranty and a 1 year labor warranty. We also talked about financing but if the system is financed it will not have the 20% off system replacement. If you have any questions please contact me and I will do my best to help you in anyway possible. Jake Kring.


ISAAC J.

ISAAC J. Job Checkin

Came out to call for a second look at a system we’ve been out to a couple of times. Customer stated that the system wasn’t cooling properly and would shut off and not come back on. We recently were out and found no issues with how the system was operating, but we replaced a fuse. I found the low voltage fuse blown again. So replaced the fuse and I went through the wiring and tested system operation. Fuse didn’t blow, but I had a hunch that the low voltage was being tampered with given there was mouse droppings present. I checked the two wire out at the condenser unit and found a decent sized mouse nest in the electrical panel of the AC system. Under its nest I found the 24v wiring chewed to shreds. Showed customer and explained what had happened and how to fix it. I fixed the 24 volt wiring, removed the nest and cycled unit back on. System was cooling properly within manufactured specifications at this time. Recommended customer change filters more often as well. He bought 3 filt