Condenser is fenced off & when I checked pressures they were higher than normal for R-22. Washed the condenser off & let the unit dry off then checked pressures again, they came down a but mentioned that fence to the condenser needs to be open because it’s not getting enough airflow. Closed it & showed him the pressures started climbing again. Had a good temperature difference inside the home with the temperature probes. Signed up for membership as well. No other issues to report.