Raheem 3 ton split system had a big leak on the condenser causing the pressures to read low. Checked the evaporator out & couldn’t see any sign of oil but it had been replaced 9 years ago & was starting to freeze up. Condenser is 16 years old. Didn’t recommend charging the system because it would eventually leak again. Will need to see if there’s a condenser coil or condenser in stock to change it out. Capacitor was also bad, rated 50, reading 3.4. No other issues to report.