Job Checkin

Service Call/ Maintenance Performed Today- Filter sizes- 18x30x1 Filter Condition- impacted Unit age- 2020 Unit condition- fair Thermostat- t6 On arrival found the following- Suction line frozen to the compressor, dirty filter, AH cabinet insulation torn & blocking the evap coil, humming, worn contactor Indoor Unit- garage Blower amps- 1.2 Blower Capacitor- na Blower Type- ECM Heat amps- 20 Drain- restricted Float Switches- works Cleanliness- fair Outdoor Unit- heat pump Compressor amps- 9.4 Outdoor fan amps- Capacitors- 69/4.84 LRA= 72.6 Pressures are- 121/350 Refrigerant type- 410a Superheat- 27 Sub-cooling- 14 Temperature difference- 20 Temp in- 57 Temp Out- 77 Duct Condition-good Insulation in Attic- good Notes- Not a recall, it’s a service call. Dirty filter, AH insulation was apart being sucked in restricting air flow, humming, worn contactor, UV Kit to curb microbial growth development, & a chemical drain line treatment w/a drain guard.system had tw