Membership maintenance Checked all wiring tested float switch function. Took indoor blower motor amp draw. Took air temperature split at supply and return. Filter does not need to be changed at this time. No microbial growth found on unit interior. Blower wheel evaporator coil clean. Took compressor and outdoor fan motor amp draws. Checked refrigerant pressures and temperatures. Tested capacitor microfarads. Capacitor was low reading 31 out of 40 µF. With homeowners approval replaced this capacitor with a turbo 200 during today’s maintenance. After replacing capacitor switched breaker back on and breaker failed. With homeowners approval got a new breaker 60 amp square DQO from City electric and replaced today. After replacing breaker ran system in cooling and stayed until system cooled the home from 80 to 77° to ensure everything was working properly. The system is running well at this time.