7-24-25 NM Arrived onsite and spoke to homeowner and listened to her complaints. Started out with high humidity. T stat reading 74 but humidity was 65 percent. Climbed into attic Checked static and it was a 0.61, Took temp split and found the temp split was only 10 degrees. Checked heat kit and found heat kit not running at this time. Climbed out of attic and checked pressures. Found high head pressure. Inspected condenser coil and found that the unit had some build up from debris and dirt. Checked again and found system was overcharged at this time. Adjusted charge and went up in attic and adjusted speed tap settings. Unit is a half ton undersized but seems to be okay. Duct work strapping is something that should be addressed but we don’t do duct work till November. Went back outside to check pressures after adjusting airflow