Today I came to Alisha and Simon’s New Brighton home to perform a furnace service before winter. Furnace service: Upon tune up and inspection of the 22 year old system I tested and adjusted the gas valve, burners, gas pressure and temperature rise. Pulled and cleaned the flame sensor. Tested ignition system, inducing motor and assembly, blower motor and assembly, heat exchanger, humidifier, static pressures, tested and tightened all electrical connections, all safety switches and control board. The furnace is in poor condition. The inducing motor is over amperage, over heating, and has bearing ware indicating impending failure. The igniter, flame sensor, gas valve, safety switches, and control board, are all working well within manufacturers specifications. The blower motor is leaking oil indicating impending failure. There is advanced corrosion around the inducing motor manifold indicating advanced heat exchanger ware. The humidifier no longer works and has been shut off. The contr