Today I came to Colleen’s Lakeview home because the furnace stopped working over the weekend. Atco came out and did the system has a drainage issue and the pressure switch is faulty. Upon inspection I can see Atco is partially correct. The system has water built up in it and the pressure switch won’t prove. Because the furnace was running, we decided to do a furnace tune up and service. Furnace service: Upon tune up and inspection of the almost 13 year old builder grade system, I tested and adjusted the gas valve, burners, gas pressure and temperature rise. Pulled and cleaned the flame sensor. Tested ignition system, inducing motor and assembly, blower motor and assembly, heat exchanger, humidifier, static pressures, tested and tightened all electrical connections, all safety switches and control board. The furnace is in poor condition. The inducing motor was full of water. Once removed I found the inducing motor is over amperage and over heating. The condensate pan is leaking in 2 p