Today I came to Tyler’s home to perform the annual family plan furnace tune up and inspection. Family plan furnace tune up and inspection: Upon tune up and inspection of the 7 year old system I tested and adjusted the gas valve, burners, gas pressure and temperature rise. Pulled and cleaned the flame sensor. Tested ignition system, inducing motor and assembly, blower motor and assembly, heat exchanger, humidifier, static pressures, tested and tightened all electrical connections, all safety switches and control board. Furnace is in fair condition. The flame sensor, ignition system, gas valve, safety switches, control board, and blower motor are all working well with manufacturers specifications. The inducing motor is over amperage indicating internal ware. The inducing motor, and condensate trap are leaking acidic condensate into the furnace causing damage and rust. The furnace is over heating with a temperature rise of 78 degrees when it should be closer to 55 degrees. This is cause