Found buderus boiler not producing hot water and after evaluation we noticed the boiler was reading 210° on the 2107 logomatic control but the boiler was cold. Retrieved the OEM boiler sensor from webbs and replaced suspected failed one. After replacing the boiler read proper temperature, and started making and circulating hot water for the indirect water tank.