As I arrived at homeowner greeting me at the front door This homeowner has a lot of cute little Poochie’s Please be aware when the front door opens He told me that the air was blowing, but it wasn’t blowing cool. I went and saw that the air handler is blowing the thermostat is calling correctly. I went out to the outside condenser and found out the compressor was on, but the compressor fan motor was not spinning after opening up the system. I told the homeowner to shut the disconnect off at the breaker box because this disconnect is freely hanging off the wall and was painted over so I cannot open it. After looking at the internals of the compressor condenser and all the components, I have found out the capacitor was blown I tested the hard kit and it’s still putting out proper specs I did not have a 70/5 on my truck so I took a 20 and added it to a 50 to create one Re-hooked up everything back to normal and the system is back on and cooling properly. I did let the homeowners