Completed full maintenance on a split system unit Checked all wiring and components Tested refrigerant levels, and temperature Tested fan and compressor amps Tested capacitor Hose down condenser coil Took temperature splits from supply and return Tested blower wheel amps Tested float switch Vacuum and flush condensate line Unit is up and operating at this time That condenser coil is very impacted and it is causing a really high head pressure. It’s not letting that compressor breathe and cooled down which will cause it to overheat and if it overheat over and over again that compressor is gonna fail. It’s already starting to fail. The amp draw on. It is way higher than it should be. The capacitor on the Herm side is also bad due to this. Customer declined both the new capacitor and a chemical cleaning of the condenser coil. The inside unit does have a lot of bacterial growth that blower wheel needs to be cleaned. Customer declined the cleaning of the blower wheel. He approved a Evap coi