As I arrived at the homeowner greeted me at the front he showed me to the upstairs unit and he showed me where the air handler was thermostat and the outdoor unit After looking at the thermostat and turning it on, we have confirmed that the air handler is turning on and blowing warm air After going outside to the condensing unit, I walked up to it and saw the fan spinning. I put my amp meter on there and only found that I was pulling condenser fan amps and when I was standing there, I heard the compressor trying to start after opening up the system and testing the capacitor in front of the homeowner we have found that the capacitor on the hermetic side is reading 0.094 after approval I’ve installed a new capacitor and tested the system and the system turns on strong and perfectly at this time, no loud noises or anything else out of the ordinary ant draws have been taken and on the condenser fan we are getting a little higher only due to the heat load of the house and the age C