Inspected air handler and evaporator coil to check for debris and dirt, coil is clean. Checked electrical connections in air handler as well as make sure the drain is cleared. Rinsed all the dirt and debris from the condensor outside. Checked the charge in the system. R22 refrigerant running at 60 psi over 125 psi with a subcooling of 9.8 and a delta T of 20 degrees. Also Took electrical reading of the compressor, capacitor, and the outdoor fan. Compressor is running at 6.8 amps, the fan is 1.2 amps, and the capacitor is within specs.