Job Checkin

Customer turned the system. Checked the condenser, both the condenser fan and compressor were running. The compressor was drawing 13.7 amps and rated for 19.2 amps. Checked the pressures. 41/255 psi. The suction temp was 77*. Checked the evap coil. 1/2 - 3/4 of the coil was frosting over. There is a freeze protection clipped to the suction line outside of the air handler. With the difference in pressures and coil frosting, it indicates that there is a restriction. The system is R22, recommend replacing the system vs replacing the evap coil.