The thermostat was blank. Checked the air handler, found a little bit of water in the pan which tripped the overflow switch. Reset the switch and vacuumed the water from the pan. Checked the pressures, the 2nd fl system is low on refrigerant. Added 1 lb 7 oz R-410a to the system. 59* supply air, 77* return air. System is operating properly