Turned the system on and the burner started, when it was up to temp the blower motor did not turn on, just buzzed. Checked the capacitor. The run capacitor is bad. Replaced the capacitor and the motor started. On start up the start winding is louder then normal, then quiets down. The motor will need to be replaced in the future.