Jason  M.

Jason M.


Job Checkin

Annual Industrial Suppression System Inspection System: 8 IND systems Inoperable Deficiency: All system pull stations need lowered Machine 3: System will not activate on pull station and Heat detector Machine 4: 4 -IND45 ABC cylinders are due for hydro test 1 20lb Nitrogen cylinder is due for hydro test Machine 32: Need 5 cylinder straps on cylinders ( too small) Machine 40 North End: Pressure Gauge on 20lb nitrogen cylinder is low. Machine 40 South End: Need 5 cylinder straps on cylinders Lower 8 pull stations 10 sticks conduit 5 pulleys 10straps 1-20lb Nitrogen cylinder hydro test 1-20lb Nitrogen cylinder pressure gauge in red needs replaced 325 degree heat detector or use other decommissioned systems present that have extra sensors 4 IND45 ABC hydro tests