use this job for sprinkler emergency call. Sprinkler Service Call
Portable Extinguishers Inspection Annual Extinguisher Inspection Equip Desc: (3) ABC(s)
Quarterly Sprinkler System Inspection 2 - Wet Risers 3- water gauges Deficiency: Both systems are due for a 5 year internal inspection and gauge replacement System is due for 5 year FDC test 2" Main drain valve continues to have a leak ( Flushed multiple times to and still leaks ) 2-5year internal inspection 1 FDC hydro test 2" main drain valve 1- 2" Union 1- 4" nipple (2") if needed 1-6" nipple 5' 2" pipe if needed Need threader
Deficiency: 4 systems are due for 5 year internal inspection and gauge replacement 2 FDC hydro tests are due Riser 1 FDC needs piped outside ( blocked from outside ) 4- 5 year inspections 2 FDC hydro test 8 water gauges 40' 4" pipe 2 4" victaulic elbows Anchors to wall or cement for 4" pipe
confirmed with Jason for 7:30am Sprinkler Inspection
confirmed with Nathan Backflow and Sprinkler Inspection
Install rebuild kit and new actuator in pre-action system Sprinkler Service Call
2 guys- 1 hour deluge +fm200 inspections Sprinkler and Special Hazards Inspection
Leave at front desk for Ryan Lytle. Sprinkler Service Call
Quarterly Sprinkler System Inspection 4- WET 8- WATER GAUGES
deliver to Lobby for Ryan Lytle. Sprinkler Service Call