Work was done in a timely manner by an excellent technician.
confirmed with Dawn for 7am. Sprinkler Inspection
Deficiency: Replace both sides of packing due smoke coming out of packing Aurora pump Type 6-481-1BB Serial # 12-2261268 Troy wants New bolt replacements for both sides and new packing
NEED CINTAS PAPERWORK Sprinkler Inspection
Semi-Annual Sprinkler System Inspection Deficiency: 1968 standard response sprinklers are due for 50 year UL testing 2- 165 degree upright 1/2” K factor 4.0 brass 2- 165 degree pendant 1/2” k factor 4.0 chrome Wet sprinkler with Alarm valve is due for the 5 year internal inspection and gauge replacement FDC hydrotest 2- water gauge. Steel threaded pipe 5 hours labor Deficiency: 1968 standard response sprinklers are due for 50 year UL testing 2- 165 degree upright 1/2” K factor 4.0 brass 2- 165 degree pendant 1/2” k factor 4.0 chrome Wet sprinkler with Alarm valve is due for the 5 year internal inspection and gauge replacement FDC hydrotest 2- water gauge. Steel threaded pipe Check valve is behind riser Need lift
Annual Sprinkler System Inspection 6 Wet Risers. Deficiency: Antifreeze loop tested at 28 degrees due to no check valve 10 gallons antifreeze needs replaced Needs data sign 1 1/2 check valve 1- 1 1/2 Union Need threader and hydro pump
confirmed with Matthew Smearman Fire Hydrant Inspection
Semi-Annual Clean Agent Suppression Inspection Equip Desc: KIDDE FENWAL 9300 -- SERVER ROOM Deficiency: Ceiling tiles are missing All ceiling tiles should have clips Install ceiling tiles with clips to hold tiles in place when system would discharge
confirmed with John Annual Fire Pump & Sprinkler inspections Fire Pump and Sprinkler Inspection