Alarm Device - Manual Station Building D Maintenance Shop 1.00 Repair of PULL STATION IN MAINTENANCE SHOP BAD. SD500-PS MANUAL PULL OR STANDARD PULL WITH SD505-MIM MODULE NEEDED TO REPLACE. REMOVED BAD PULL AND DELETED POINT FROM PROGRAMMING UNTIL SOLUTION IS DETERMINED.