Trane furnace repair , intermittent dual pressure errors , low fire pressure switch closes about half the time . I inspected vents with my inspection camera and found no blockages . Verified drain is clean and flowing . Pressure switches need 1.05 and 1.60 inw to close and the furnace has no problem reaching upwards up 2.0 inw . I have recommended dual pressure switch be replaced .