Steve was able to help us purchase a furnace that fit our needs and budget.
Great customer service, called yesterday and had someone out the next day. The tech was professional and knowledgeable. Would definitely recommend and use Evan’s again.
I have never been sorry that I chose Evans. Jordan is an excellent service technician and very capable.
The service tech was very professional. Was very thorough and explained what he was doing. I was totally impressed by his work ethics. A real asset to your firm. The only reason I gave the pricing a 4 star rating was that the $148.00 seemed, if my memory serves me, quite a bit higher than the last time. But I realize like everything else, your costs have increased, so it is not an issue with me. I will continue to use your company in the future. Thank you for your good service.
Jordan is definitely an excellent technician, very polite, answered all my questions , would recommend him to others,
The furnace installation went very well. Joe and Brendan arrived on time and finished in good time.
Thanks again for the great service. Always punctual and professional and technician reviews service at completion of appointment
I could not say enough good stuff about Chris. He explained everything to me in detail and also the what ifs. He was very very professional and would definitely recommend him to others. We don’t want to deal with anyone else.
Response from Evans Heating & Cooling:
Thanks for sharing your rating with us and the community.
Jordan the service technician was excellent. He arrived early, was nice, respectful and efficient. He answered any questions I had. He left the area he worked on very clean. I was very happy with Jordan and Evans Heating and Cooling. I will be using them for all my heating and air conditioning needs.
Response from Evans Heating & Cooling:
Thank you so much for taking the time to leave an excellent rating. We really appreciate your business.
Response from Evans Heating & Cooling:
Your kind words mean a lot to us. Thanks for the positive feedback.
Installed hot water tank and chimney liner
Lennox boiler repair. Pilot flame was partially clogged causing burners not to light consistently. Cleaned pilot and burners and put boiler back together. Pilot light is now much stronger and boiler is lighting consistently first try. No other problems found, working well at this time.
Keeprite furnace repair Furnace was cycling on high limit causing ecobee to recalibrate every morning. Airflow was being restricted by filter with high merv rating, filters were coming too restrictive in just a few weeks. Allergies, etc. are not a concern so a lower rated filter (merv8, merv11, etc.) is recommended to solve this issue. No problems found with the furnace itself.
Bryant furnace , error code 3.1 failed pressure switch . Verified drains and venting are clear of debris . All 3 pressure switched where closing . Furnace was not sending 24 volts to high pressure switch . I removed circuit board to inspect front and back , also tapping the relays . When I reinstalled board furnace operated without issue . C.0 in the exhaust was over 150 ppm , I adjusted gas pressure on high side down to 2.9 inw ( factory recommended 3.2 to 3.8 ) which brought c.o down to 70 ppm on low and high fire . Possible small blockage in secondary heat exchanger . If problem persist with pressure switch error the circuit board will be to be replace or the furnace .
Furnace repair Furnace igniter would light, no flame. Gas valve is getting 24 volts. Wired gas valve directly to 24volt transformer to discover the gas valve is defective. Replaced gas valve and gas valve would partly open. Wired new gas valve directly to 24 volts and gas valve would open. Ensured gas valve was getting 24 volts and then inspected control board and found a small burn mark. Control board will require replacement as well. Customer is going to receive quotes on a new furnace.
Furnace and tankless maintenance and inspection. Both are working well and in good condition at this time.
Carrier furnace repair , inducer motor is starting to fail , recommended maintenance if he replaces motor
Lennox furnace repair , installed new pressure switches tested unit for 12 mins
Lennox furnace maintenance, cleaned replaced and tested humidifier pad , furnace is operating good
Lennox furnace maintenance, furnace operating correctly , high fire pressure switch failed open , I have recommended to replace switched
Keeprite furnace maintenance , removed and cleaned condensation pump , removed inducer motor to check condition of collector box , test unit , furnace in good working order