Performed a heating maintenance. Oil boiler. Changed the nozzle filter and strainer. Adjusted electrodes. Purged the oil line. Cleaned the heat exchanger and flue pipe. Recemented the flue pipe. Started and tested. Combustion test was 4ppm at 4.5%o2. No smoke on the smoke test.